Anchor test and lock-off loads

Lock-off load, proof load of acceptance tests to EN 1997-1 A1:2013, tendon limits, load steps, expected elongation and the apparent free tendon length band, with a check of measured readings.

Anchor load
Pk = FServ,kkN
γE-
Ed (ULS)kN
Life
EULS,d = max(Ed, γServ Pk), EN 1997-1:2004 + A1:2013 (8.3).
Geometry
z0 headm
α below horiz.°
Lfreem
Lbondm
Ddrillmm
kD = Dbond/D-
Spacingm
zw GWTm
L to slip surfacem
H wallm
Tendon
Type
Strands-
Bar Ø
Atmm²
Ptk ultimatekN
Pt0.1k yieldkN
τk grout–tendonMPa
Partial and model factors
γServ-
γa,ULS-
γRd model-
γs tendon-
γC grout-
ψ cone°
Bolt
Type
dmm
Corrosion lossmm
Yield loadkN
Ultimate loadkN
Outer Ømm
Dholemm
L boltm
Depth to jointm
Plate / nutkN
Bond
τ rock–groutkPa
τ grout–barkPa
Rock–grout: weak rock 300–800, medium 700–1500, strong 1500–3000 kPa (Littlejohn & Bruce 1977; Wyllie 1999). Resin and friction bolts: enter the per-metre value from pull tests.
Basis and pattern
Basis
Design approach
Span Bm
ESR-
Spacing sm
Test and lock-off
P0 / Pk-
Method
Anchor
Ground at bond
Le jackm
Tendon, lengths and loads come from the ground anchor tab. Loading sequences of EN ISO 22477-5:2018.
Ground layers
Bond per layer: qs unit skin friction (soil, from tests or tables) or rock–grout bond stress; MC Mohr–Coulomb interface with K0; Lendi (1978). Blank K0 = 1 − sin φ′.
Typical ultimate qs [kPa]
Soft to stiff clay (gravity grouted)30–70
Stiff to hard clay (pressure grouted)70–250
Silt, loose sand70–140
Medium dense sand100–250
Dense sand, sandy gravel (pressure grouted)200–400
Weak rock: marl, weathered shale, chalk300–800
Medium rock: sandstone, weathered limestone700–1500
Strong rock: limestone, dolomite, granite1500–3000
FHWA-IF-99-015; Littlejohn & Bruce (1977); Wyllie (1999). Rock: roughly σc/10 to σc/30, at most about 4 MPa. Confirm with tests.
Design resistance against bond length
Capacity against anchored length
Load–displacement at the head
Use Tk in the rock stability tools
Planar and wedge sliding open with the bolt capacity Rk = Tk. Tunnel wedge opens with Tk = min(steel, plate), the bond per metre and the bolt length, and finds the length beyond the joint itself. Each tool applies its own partial factor γa.
Design basis

Actions (EN 1997-1:2004 + A1:2013, Section 8 Anchors): EULS,d = max(Ed, γServ FServ,k) with γServ = 1.35; Ed from the ULS analysis, here γE Pk unless entered.

Ground resistance: RULS,d = RULS,k/γa,ULS, γa,ULS = 1.1 (recommended values of Annex A; check your national annex). RULS,k comes from investigation or suitability tests (EN ISO 22477-5). For preliminary design the tool calculates it from the ground and divides by a model factor γRd: qs: π D qs L; Mohr–Coulomb: 2πRc′L + πRσ′v[K0(1 + sin²α) + cos²α] tan φ′ L; Lendi (1978): 8Rσ′v tan φ′ L / [cos²α + sin²α(1 + 2 tan²φ′) + 2 sin α cos α] + 2πRc′ cos²φ′ L. σ′v is integrated along the bond through the layers and the water table.

Tendon: Rt,d = Pt0.1k/γs (strands Y1860S7 to EN 10138-3, bars fyk), γs = 1.15. Service load P ≤ 0.65 Ptk and lock-off P0 ≤ 0.60 Ptk (EN 1537, Annex D). Grout–tendon: perimeter × Lbond × τk/γC.

Ground cone (Littlejohn & Bruce 1977): effective weight of a cone with its apex at the middle of the bond against the vertical component, for anchors steeper than 10°; for a row of anchors the volume per anchor is limited to s·h²·tan ψ; γG,stb = 0.9.

Detailing (FHWA-IF-99-015, Sabatini et al. 1999): bond zone ≥ max(1.5 m, H/5) behind the critical slip surface, ≥ 4.5 m of ground over the bond, spacing ≥ max(4 D, 1.2 m), bond 3–10 m; free length ≥ 5 m as common practice (NF P 94-282; EN 1537 leaves the minimum free length to the design of the structure).

Rock bolts: Tk = min(steel yield, embedded side, head side): embedded side = min(rock–grout, grout–bar) bond over the length beyond the joint, head side = plate + bond within the block (Hoek, Kaiser & Bawden 1995). EN 1997 basis: Td = Tk/γa (Table A.12: R1/R2 1.1, R3 1.0), as in the slope and tunnel wedge tools. Length rules: L = 2 + 0.15 B/ESR (NGI Q-handbook), L ≥ 2 s (Lang 1961).

Tests (EN 1997-1 A1:2013, EN ISO 22477-5, EN 1537): proof load Pp ≥ γa,acc,ULS EULS,d (test methods 1 and 2, 1.1) or ≥ γa,acc,SLS FServ,k (method 3, 1.25); Pp ≤ min(0.95 Pt0.1k, 0.80 Ptk); datum load Pa = 0.10 Pp. Apparent free tendon length Lapp = Et At Δsel/(Pp − Pa) from the unloading (EN ISO 22477-5 Annex D) between 0.8 Lfree + Le and Lfree + Le + 0.5 Lbond (bond type) or 1.1 Lfree + Le (compression type), EN 1537. Load steps and observation periods: EN ISO 22477-5:2018 Tables 4, 8 and 11 (acceptance tests); the limits α1, kl are in the national annex to EN 1997-1.

About this tool

For a prestressed ground anchor the page gives the lock-off load P_0, the proof load of acceptance tests P_p = 1.1 E_ULS,d (test methods 1 and 2) or 1.25 F_Serv,k (method 3) to EN 1997-1:2004 + A1:2013, and checks it against the tendon (P_p at most min(0.95 P_t0.1k, 0.80 P_tk)) and the lock-off load against 0.60 P_tk (EN 1537).

It lists the acceptance test loading steps and observation periods of EN ISO 22477-5:2018 for test methods 1, 2 and 3, from the datum load P_a = 0.1 P_p, and the elastic elongation between P_a and P_p for the lower and upper limits of the apparent free tendon length (0.8 L_free + L_e and L_free + L_e + 0.5 L_bond, or 1.1 L_free + L_e for compression anchors). Paste measured load and displacement readings to get the apparent free length from the unloading and see whether it lies within the band.

The creep and load loss limits (α1, k_l) are those of the national annex to EN 1997-1; the recommended values are shown.

Related tools

Free to use, no sign-up. Results are for checking and preliminary design; verify them for your project. Questions or ideas: [email protected].