Anchor test and lock-off loads
Lock-off load, proof load of acceptance tests to EN 1997-1 A1:2013, tendon limits, load steps, expected elongation and the apparent free tendon length band, with a check of measured readings.
Found this tool useful?
koplemo is free, with no ads and no sign-up. It is kept running by the engineers who use it.
Payment handled by Stripe. We never see your card details.
Payment handled by Stripe. You can cancel at any time; write to [email protected] if you need help.
About this tool
For a prestressed ground anchor the page gives the lock-off load P_0, the proof load of acceptance tests P_p = 1.1 E_ULS,d (test methods 1 and 2) or 1.25 F_Serv,k (method 3) to EN 1997-1:2004 + A1:2013, and checks it against the tendon (P_p at most min(0.95 P_t0.1k, 0.80 P_tk)) and the lock-off load against 0.60 P_tk (EN 1537).
It lists the acceptance test loading steps and observation periods of EN ISO 22477-5:2018 for test methods 1, 2 and 3, from the datum load P_a = 0.1 P_p, and the elastic elongation between P_a and P_p for the lower and upper limits of the apparent free tendon length (0.8 L_free + L_e and L_free + L_e + 0.5 L_bond, or 1.1 L_free + L_e for compression anchors). Paste measured load and displacement readings to get the apparent free length from the unloading and see whether it lies within the band.
The creep and load loss limits (α1, k_l) are those of the national annex to EN 1997-1; the recommended values are shown.