Steel fibre shotcrete lining M-N (fib MC2020): worked example
M-N resistance of a 250 mm steel fibre shotcrete lining without bars by fib Model Code 2020: rigid-plastic fibre tension, pure tension, pure bending and MRd at 1000 kN/m by hand.
Open this example in the tool The link loads all inputs below.
Problem
A tunnel is supported by 250 mm of steel fibre shotcrete with no bars. At the crown, the design forces from the numerical model are NEd = −1000 kN/m (compression) and MEd = 60 kNm/m. Is the lining strong enough, and what does the fibre tension add?
| Section | b = 1000 mm (per metre of tunnel), h = 250 mm, no reinforcing bars |
| Concrete | C30/37, γC = 1.5, ktc = 0.85, parabola-rectangle with εc2 = 2.0 ‰, εcu = 3.5 ‰ |
| Fibres | steel, class 4.0c: fR,1k = 4.0 MPa, fR,3k = 3.6 MPa; γSF = 1.5, κO = 1.0 |
| Tension model | rigid-plastic, ultimate tensile strain εFu = 20 ‰ |
| Design forces | NEd = −1000 kN/m, MEd = 60 kNm/m |
The method is the cross-section design of fibre reinforced concrete in the fib Model Code 2020 (chapters 18 and 30). The concrete in compression follows SIST EN 1992-1-1:2024. The numbers are our own case.
1. Materials
The rigid-plastic law puts a constant stress fFtu,d over the whole tension zone. κG is the size factor of SIST EN 1992-1-1:2024 (L.6). The tool applies it with the fib approach as well, and you can switch it off. Per metre of lining, Act = 1.0 · (h − x).
2. Pure compression and pure tension
Unlike plain concrete, the fibre section carries a tension force. In compression the tool caps the diagram at the minimum eccentricity e0 = max(h / 30, 20 mm) = 20 mm, which gives NRd,max = −3472 kN/m.
3. Pure bending (N = 0)
The bottom face reaches εFu = 20 ‰. The compression zone is then so shallow that the top strain εc stays below 2 ‰, on the parabola. For a top strain εc (in ‰):
Setting Fc = Ft takes a couple of trial values. εc = 1.0 ‰ gives Fc = 84 kN < Ft = 213 kN, and 2.0 ‰ gives 258 > 203 kN. Equilibrium is at εc = 1.714 ‰:
The quick estimate fFtu,d κG h² / 2 = 0.800 · 1.115 · 0.25² / 2 = 27.9 kNm/m ignores the depth of the compression zone and is 6 % high.
4. Moment resistance at NEd = −1000 kN/m
With this much compression the top face reaches εcu = 3.5 ‰. The full parabola-rectangle block has α = 1 − εc2 / (3 εcu) = 0.810 and ka = 0.416. Find x from Fc − Ft = 1000 kN/m:
Of the 109.5 kNm/m, the fibre tension contributes 6.0 kNm/m directly. It also deepens the compression zone, because the concrete has to balance Ft as well as N.
5. Check of the design point
Both measures show that the lining is adequate at the crown. The ray scales M and N together, as a load factor on one load case would.
Result in the tool
| Hand calculation | Tool | Difference | |
|---|---|---|---|
| fcd / fFtu,d | 17.0 / 0.800 MPa | 17.00 / 0.800 MPa | 0 % |
| Pure compression / pure tension | −4250 / 225 kN/m | −4250 / 225 kN/m | 0 % |
| MRd at N = 0 | 26.2 kNm/m | 26.2 kNm/m | 0 % |
| MRd at N = −1000 kN/m | 109.5 kNm/m | 109.5 kNm/m | 0 % |
| NRd,max (e0 = 20 mm) | – | −3472 kN/m | |
| Utilisation of the design point | 0.45 (ray) | ηmax = 0.45 | 0 % |
The link at the top opens the FRC tab of the M-N tool with this section and the design forces pasted as an Excel table, with γG set to 1.0 because they are already design values. The FRC tab asks for a password. The Diagram button copies the whole curve, so you can read MRd at any axial force.
Your own case
- Take fR,1k and fR,3k from the beam tests of your mix (EN 14651), not from the class alone. The class only gives lower bounds.
- Choose Linear instead of rigid-plastic for the softening law through fR,1 and fR,3, or SIST EN 1992-1-1:2024 Annex L to compare the two standards (κO is then usually 0.5).
- For young shotcrete, enter its age t: the tool reduces fck to fck(t).
- Paste the lining forces of a whole model from ZSoil, RS2 or DIANA, and check shear on the Shear tab.
- Synthetic fibres need a creep factor for the residual strength, and the tool warns where a permanent lining needs more than this check.
References
- fib (2023). fib Model Code for Concrete Structures 2020. International Federation for Structural Concrete, Lausanne, chapters 18 and 30.
- SIST EN 1992-1-1:2024 (= EN 1992-1-1:2023). Eurocode 2: Design of concrete structures, Part 1-1, clause 5.1 and Annex L.
- EN 14651:2005+A1:2007. Test method for metallic fibre concrete: measuring the flexural tensile strength.
Worked example by Martin Hostnik, updated 2026-11-21. Results are for checking and preliminary design; verify them for your project. Questions or a correction: [email protected].